Lochinvar Knight XL KBN501 Boiler Instruction Manual

Manual Lochinvar Knight XL KBN501 Boiler Instruction Manual

Lochinvar Knight XL KBN501 Boiler Instruction Manual

5/5 (1👤)
📕 Manual PDF 📄 16 Pages
★Rate It★

How many stars do you give this manual?

Lochinvar Knight XL KBN501 Boiler

Full Screen

Lochinvar Knight XL KBN501 Boiler

Full Screen

Lochinvar Knight XL KBN501 Boiler

Full Screen

Lochinvar Knight XL KBN501 Boiler

Full Screen

Lochinvar Knight XL KBN501 Instructions

Here we offer the Lochinvar Knight XL KBN501 Boiler manual completely free and in English. We have cataloged this manual in the Boilers section on Manualverse, and it has been rated by 1 users with an average rating of 5. If you have any specific questions about Lochinvar Knight XL KBN501 Boiler, we suggest checking the Frequently Asked Questions (FAQs) section of this manual.


Product Images

Imagen 1
Imagen 2
Imagen 3
Miniatura 1
Miniatura 2
Miniatura 3

Lochinvar Knight XL KBN501 Boiler Specifications

Specification Value (KBN501)
Model Number KBN501
Input MBH Gross 500
Net AHRI Output MBH 470
AHRI Boiler Water, MBH 409
Water Content (Gallons) 4.2
Water Connections 1-1/2" NPT
Gas Connections 1" NPT
Air Inlet Piping Size 4" (102 mm)
Vent Piping Size 4" (102 mm)
Maximum Allowed Working Pressure 50 PSI (344.7 kPa)
Minimum Combustion Air/Vent Piping Length 12 equivalent feet (3.7 m)
Maximum Combustion Air/Vent Piping Length 100 equivalent feet (30.5 m)
Standard Operating Altitude Sea level to 4,500 feet (derates 4% per 1,000 feet above 4,500 feet)

Lochinvar Knight XL KBN501 Boiler Details

The Lochinvar Knight XL KBN501 boiler utilizes an advanced stainless steel heat exchanger, specifically designed with coils to ensure maximum heat transfer efficiency and superior protection against flue gas corrosion. This innovative design enables fully condensing operation, a key factor in achieving its high efficiency ratings. The boiler's combustion process is carefully contained within a jacket housing these coils, optimizing performance and extending the product's lifespan through reduced stress on materials.

At the core of the KBN501 is the sophisticated SMART SYSTEM Control Module. This intelligent control unit constantly monitors inputs from various boiler sensors and external devices, precisely regulating the blower and gas valve. It accurately adjusts the boiler's firing rate across a wide 20% to 100% modulation range. This broad modulation capability ensures optimal performance by precisely matching heat output to the current heating demand, significantly enhancing both energy efficiency and occupant comfort by maintaining stable temperatures.

The SMART SYSTEM offers highly adaptable temperature control, with boiler operation configurable based on boiler outlet water, return water, or system supply temperature. It provides three individual user set points for versatile zone control, prioritizing the highest demand for responsive heating. An "Outdoor Air Reset" function dynamically adjusts setpoints based on ambient conditions, further optimizing energy consumption. Additionally, a "Boost Function" can temporarily increase the setpoint if a space heating demand persists, ensuring comfort in varying conditions.

Robust safety is integral to the KBN501's design. The system incorporates gradient limiting, which intelligently reduces the firing rate if the outlet temperature rises too quickly, preventing thermal stress. Comprehensive high limit operations include both adjustable automatic and manual reset options, offering layered protection against overheating. Furthermore, integral low water cutoff protection ensures boiler shutdown in the event of insufficient water flow, enhancing operational safety and guarding the heat exchanger.

For reliability and ease of management, the boiler includes essential features like an anti-cycling mechanism to minimize wear from frequent starts, and ramp delay for smooth ignition. It continuously monitors external limits such as flow switches and gas pressure switches. The control supports seamless integration with Building Management Systems (BMS) via a 0-10V input for external control, and tracks run-time, cycle counts, and logs the last 10 errors. A customizable service reminder feature proactively notifies users of necessary maintenance, ensuring sustained optimal performance.

Frequently Asked Questions (FAQs)

Can't find the answer you need? Here are some frequently asked questions about the Lochinvar Knight XL KBN501 Boiler, and we answer them below.


What should I do if I smell gas near my KBN501 boiler?
Do not try to light any appliance, do not touch electrical switches or use any phone in the building. Immediately call your gas supplier from a nearby phone, or the fire department if unreachable.

How often does the KBN501 boiler require maintenance?
The boiler should be inspected and started annually by a qualified service technician. Additionally, owner maintenance, including checking the boiler area, pressure gauge, and vent piping, should be performed daily to every six months, as detailed in the manual.

What water quality is recommended for the KBN501 boiler?
It's critical to maintain boiler water quality with hardness between 5-12 grains/gallon, pH between 6.5-8.5, Total Dissolved Solids (TDS) less than 350 ppm, and chlorine concentration less than 150 ppm. Continual fresh makeup water should be avoided as it reduces boiler life.

Can corrosive contaminants damage the KBN501 boiler?
Yes, do not install the boiler in environments with corrosive contaminants like chloro/fluorocarbons, chlorine-based chemicals (e.g., from pools or laundry), or muriatic acid, as these can damage the boiler and lead to flue gas spillage or water leakage.

What type of antifreeze is safe to use with the KBN501 boiler?
Use only inhibited propylene glycol solutions specifically formulated for hydronic systems. NEVER use automotive antifreeze (ethylene glycol) as it is toxic and can damage system gaskets and seals.

What if my KBN501 boiler has been submerged in water?
Do not use this boiler if any part has been under water. Flooded appliances can incur extensive damage and present numerous safety hazards, requiring immediate replacement.

What is the SMART SYSTEM control module?
The SMART SYSTEM Control Module is the boiler's electronic brain. It receives sensor inputs, regulates the blower and gas valve to meet heating demands, and manages pumps. It offers user-programmable settings for temperature, operating modes, and safety functions.

What materials are approved for the KBN501's venting system?
The Knight XL requires a special venting system. Only approved stainless steel, PVC, CPVC, or polypropylene pipe and fittings listed in the manual are to be used for vent pipe and fittings. Mixing components from different systems is not allowed.

What are the gas pressure requirements for the KBN501?
For Natural Gas, the inlet pressure at the gas valve should be a maximum of 14 inches w.c. (3.5 kPa) and a minimum of 4 inches w.c. (0.99 kPa) with gas flowing. For Propane Gas, it should be a maximum of 14 inches w.c. (3.2 kPa) and a minimum of 8 inches w.c. (1.9 kPa) with gas flowing.

Does the KBN501 boiler derate at higher altitudes?
Standard KBN501 boilers operate from sea level up to 4,500 feet with no adjustments. Above 4,500 feet, the boiler will derate by 4% for each 1,000 feet. High altitude models (3,000 to 12,000 feet) derate by 2% for each 1,000 feet above sea level.

Does the KBN501 have low water cutoff protection?
The SMART SYSTEM control module incorporates temperature sensing to ensure boiler shutdown in low water or low flow conditions. An optional low water cutoff device (100173646) is available and may be required by local codes.